Plumbing Calculation
1. INTRODUCTION
1.1. Project Description
This calculation covers the
plumbing system for Office Building-B, Warehouse & Workshop and Electrical
Building. Potable water will be supplied from Main line. While Black and Waste
Water will be discharged to Septic tank. Then treated water will be directed to
drainage by free flowing/gravity.
1.2. References
This
calculations are based on the following documents:
1.2.1. Standard and Codes :
§ International
Plumbing Code 2009 (IPC 2009)
§ National
Plumbing Code 2006 (NPC 2006)
§ Standar
Nasional Indonesia (SNI) no. 03-7065-2005 Tata Cara Perencanaan Sistem Plambing
§ Peraturan Menteri Negara Lingkungan Hidup Nomor 03 Tahun
2010 tentang Baku Mutu Air Limbah bagi Kawasan Industri
§ Pedoman
Plambing Indonesia (PPI) 1979
1.2.2. Reference Book
§ Soufyan, Morimura : Perancangan dan
Pemeliharaan Sistem Plambing; 1991, Pradnya Paramita.
2. OBJECTIVES
The
purposes of this Plumbing calculation are to determine:
a) Potable
cold water main pipe size
b) Sanitary
drainage (Black & Waste water) and vent main pipe size
c) Septic
Tank Capacity
3. DESIGN BASIS AND ASSUMPTION
3.1. Design Basis
3.1.1. Potable Water Demand
a. Potable
water demand calculation is based on the occupants water demand.
b. Potable
water demand for 1 occupant is based on Standard of Potable Water Consumption
per Day (SNI 03-7065-2005). See Appendix-2.
3.1.2. Potable Water Pipe
a. Potable
water flow is determined using fixture unit method.
b. Potable
water supply fixture unit (WSFU) is based on the table below.
Table.1 Water Supply Fixture Unit
Plumbing Fixture/Group
|
Type of Supply Control
|
Fixture Units
|
Lavatory (Public)
|
Faucet
|
1
|
Lavatory (Private)
|
Faucet
|
1
|
Service sink/Janitor
|
Faucet
|
3
|
Shower head (Public)
|
Mixing valve
|
2
|
Shower head (Private)
|
Mixing valve
|
2
|
Urinal (Public)
|
Flush tank
|
2
|
Water Closet (Public)
|
Flush tank
|
2.5
|
Water Closet (Private)
|
Flush tank
|
2.5
|
Reference: Table of Water Supply Fixture Units (WSFU) and Minimum Fixture Branch Pipe Size, UPC 2000 (Appendix-3).
c. Total
of WSFU used to determine peak flow rate using Potable water fixture unit –
flow Chart from Figure of Estimate curve
for demand load, ASHRAE handbook Fundamental 2009 (Appendix-4).
d. Potable
water pipes size are determined using Hazen William Table for :
- PVC
pipe (Appendix-5)
e. Potable
water distribution piping which is supply close to a plumbing fixture, follow
to Water Supply Fixture Units (WSFU) and Minimum Fixture Branch Pipe Size, UPC
2000 (Appendix-3).
f. Minimum
flow pressure required is based on Standard of minimum flow pressure required
for Plumbing Fixture, IPC 2009 (Appendix-6).
3.1.3. Black and Waste Water Pipes and Vent Pipe Sizing
b.
Drainage fixture units are refer to table below
Table.2
Drainage Fixture Unit
Plumbing Fixture/Group
|
Fixture Units
|
Kitchen sink (Public)
|
3
|
Lavatory
|
1
|
Service sink/Janitor
|
2
|
Urinal (Public)
|
2
|
Water Closet (Public)
|
4
|
Water Closet (Private)
|
3
|
Floor Drain
|
2
|
Reference:
Table of Drainage Fixture Unit Values (DFU)
UPC
2000 (Appendix-7)
c. Black
and Waste water pipes and sewer pipes size are determined by table of Maximum
Unit Loading and Maximum Length of Drainage and Vent piping (Appendix-8) with
1% minimum slope.
d. Vent
pipe size determined by table of Maximum
Unit Loading and Maximum Length of Drainage and Vent piping (Appendix-8)
3.1.4. Septic Tank
a. All
of Black and Waste water will be drained and treated in septic tank before
discharged to external drainage
b. Septic
tank capacity is based on total capacity of disposal Black and waste water per
day
c. Disposal
of Black and waste water determined based on number of occupants
d. Septic
tank will use Bio filtration system (packaged by vendor)
3.2. Assumptions
The
following assumptions are considered for the calculations:
- Maximum
recommended velocity of potable water pipe to be limited at 2.4 meter/second to
get low friction (NPC 2006),
- Sloping
of Black & gray water pipe within the building shall be minimum 1% refer to
table of Maximum Unit Loading and Maximum Length of Drainage and Vent piping
(Appendix-8)
- Maximum
flow friction, within the pipe is 100 mm/m
3.3. Pipe Data
Table.3
Material of Plumbing Pipe Inside Building
Service
|
Material
|
Class
|
Potable cold water pipe
|
uPVC
|
10 kg/cm2 (AW Class)
|
Black and Waste water pipe
|
uPVC
|
10 kg/cm2 (AW Class )
|
Vent pipe
|
uPVC
|
5 kg/cm2 (D Class )
|
4. CALCULATIONS
1) Potable
Water Demand
a. Potable
water demand = no. of occupant (person) x Water Demand standard (ltr/psn/day)
b. No.
of Occupant:
- Office
Building-B : Refer to PSB-E-00-A5-DW-030/ PSB-E-00-A5-DW-031
- Warehouse
& Workshop : Refer to
PSB-E-00-A5-DW-048/
PSB-E-00-A5-DW-049/ PSB-E-00-A5-DW-050
- Electrical
Building : Refer to DBAC914300
c. Water
demand standard refer to table “Pemakaian air dingin minimum sesuai penggunaan
gedung” (Appendix-2)
2) Distribution
of Potable Water Main Pipe Size
a. Calculation
Quantity of Plumbing Fixture :
- Office
Building-B : Refer to PSB-E-00-A5-DW-030/ PSB-E-00-A5-DW-031
- Warehouse
& Workshop : Refer to
PSB-E-00-A5-DW-048/
PSB-E-00-A5-DW-049/ PSB-E-00-A5-DW-050
- Electrical
Building : Refer to DBAC914300
b. Calculation total of fixture refer to water supply
fixture unit table, UPC page 55 (Appendix-3)
c. With
chart of Estimate Curve for Demand Load
(Appendix-4), specify flow rate by entering Total of fixture unit in the chart
d. With
the chart of “Kerugian gesek dalam pipa PVC” (Appendix-5), specify pipe size by
entering flow rate & max. velocity standard (2.4 ) (Appendix-9)
3) Black
and Waste Water Main Pipe Size
a. Calculation
Quantity of Plumbing Fixture :
- Office
Building-B : Refer to PSB-E-00-A5-DW-030/ PSB-E-00-A5-DW-031
- Warehouse
& Workshop : Refer to
PSB-E-00-A5-DW-048/
PSB-E-00-A5-DW-049/ PSB-E-00-A5-DW-050
- Electrical
Building : Refer to DBAC914300
b. Calculation total of Drainage Plumbing Fixture (DFU)
refer to drainage fixture unit table, UPC page 62 (Appendix-7)
c. With
table of Maximum Unit Loading and Maximum Length of Drainage and Vent Piping
(Appendix-8), enter the DFU pipe size using the limit of pipe slope 1%
4) Capacity
of Septic Tank
a. Capacity
of Septic Tank = no. of Population (person) x total of Black & waste water
(liter/prsn/day) x retention time ( 1 day)
b. no.
of Population taken from total of occupant at potable water demand table
(calculation sheet-1, Appendix-1)
c. total
of Black & waste water taken from potable water demand table (calculation
sheet-1, Appendix-1)
Calculation Sheet detail are
presented in Appendix-1